Обзор
Line filter
In plants with strict EMC requirements, line filters work together with line reactors to restrict the conducted interference emanating from the Power Modules to the limit values of Class A1 as defined in EN 55011 and Category C2 as defined in EN 61800-3. Line filters are suitable only for direct connection to TN systems.
The use of other makes of line filter can lead to malfunctions or irreparable damage to equipment.
Note:
According to product standard IEC 61800-3, RFI suppression commensurate with the relevant rated conditions must be provided and is a legal requirement in the EU (EMC Directive). Line filters and line reactors are required for this purpose.
The machine manufacturer must provide verification that the machinery to be operated with the drive products and the installed suppression elements, e.g. line filters, are CE-EMC compliant.
Заказные данные
Suitable for SINAMICS S120 Combi |
SINAMICS line filter |
||
|---|---|---|---|
|
Rated Infeed |
Power Module |
||
kW |
Type |
Frame type |
Article No. |
16 |
6SL3111-3VE21-6FC1 |
B11 |
6SL3000-0BE21-6DA0 |
16 |
6SL3111-4VE21-6FC1 |
B14 |
|
Технические данные
Article No. |
6SL3000-0BE21-6DA0 |
Product brand name |
SINAMICS |
Product designation |
Line filter |
Rated current |
36 A |
Rated infeed power |
10 kW, 16 kW, 20 kW |
Power loss at rated operation |
0.012 kW, 0.015 kW, 0.016 kW |
|
Line/load connection L1, L2, L3/U, V, W |
Screw-type terminals |
|
10 mm2 |
PE connection |
M6 screw stud |
Degree of protection |
IP20 |
Width |
50 mm (1.97 in) |
Height |
429 mm (16.89 in) |
Depth |
226 mm (8.90 in) |
Net weight |
5 kg (11 lb) |
Certificate of suitability |
cURus |