Обзор
- Option for SIMATIC WinCC Runtime Advanced and WinCC Runtime Professional for logging process values and alarms
- Logging of process values and alarms supports the acquisition and processing of process data from an industrial plant or machine. Evaluation of the logged process data provides information about the operating states of the plant or machine
- Licensing:
- SIMATIC Panels / Multi Panels / Comfort Panels:
No license is required. - WinCC Runtime Advanced:
One license is required per operator station - WinCC Runtime Professional:
500 Logging Tags are already included in the basic package
The number of Logging Tags can be increased by means of additional licenses
- SIMATIC Panels / Multi Panels / Comfort Panels:
Особенности
- Alarm and process value logs enable predictive diagnostics, which avoids downtimes
- Early detection of danger and fault conditions
- Increase of the product quality and the productivity thanks to regular analysis of the alarm and process value logs
Область применения
- Transfer of the logs for evaluation and long-term archiving
- Detection of recurring error states
- Optimization of maintenance cycles
- Ensuring quality standards
- Quality assurance and checking the utilization of production sequences
- Documentation of process sequences
Функции
- Time-controlled as well as manual or process-controlled swapping out of process data and alarms for long-term archiving
- During runtime, swapped out data are read in and selectively analyzed using WinCC Runtime Professional
- Presentation and evaluation of archived process data based on a configurable trend display. Reading of the values is facilitated by a read line.
- Presentation and evaluation of archived alarms based on a configurable alarm view.
- User-friendly navigation in the logs
- External evaluation of the logs using MS standard tools
- Various log types are supported: sequence and circular logs
- Logging of process values and alarms on external, Windows-supported storage media
- SIMATIC Panels and WinCC Runtime Advanced: CSV files, RDB files, Microsoft SQL Server via ODBC
- WinCC Runtime Professional: Microsoft SQL Server
- Powerful standard functions permit user-friendly and flexible utilization of the logs
Технические данные
WinCC Logging for Runtime Advanced |
|
|---|---|
The values specified are maximum values |
|
Number of logs |
100 |
Archivable data |
Process values, alarms |
Cyclical trigger for archiving process values (variables) |
1 s |
Max. number of entries per log |
500,000 1) |
Log types |
Circular logs, |
Data storage format |
CSV (Comma Separated Variable), |
1) Dependent on memory medium used
WinCC Logging for Runtime Professional |
|
|---|---|
The values specified are maximum values |
|
Number of logs per single-user station/server |
100 |
Archivable data |
Process values, alarms |
Measured values per second, max. |
Server/single-user station: 5 000 per sec. |
Log tags per single-user station/server |
80,000 2) |
Log types |
Circular log with and without long-term logging |
Data storage format |
Microsoft SQL 2008 database |
2) Dependent on the Logging PowerPack used for the log tags. 500 log tags are contained in the basis version.
Дальнейшая информация
More information is available on the Internet at: