Обзор
Thanks to its stepped profile design, the LOGO!Power product line is ideally suited for installation in small distribution boards. The stabilized power supplies with wide-range input are available with an output voltage of 24 V in four performance classes. The 24 V variants are ideal for supplying LOGO! PLCs with the corresponding voltage input.
To further increase the 24 V availability, the LOGO!Power power supply units can be combined with DC UPS, redundancy and selectivity modules.
Product highlights
- 1-phase, 24 V DC/ 0.6 A, 1.3 A, 2.5 A and 4.0 A
- Input voltage 100 … 240 V AC (85 … 264 V), 110 … 300 V DC
- Narrow unit with width of 18 mm, 36 mm, 54 mm or 72 mm and overall depth of 53 mm in LOGO! design
- Up to 90% efficiency
- Integrated current monitor: Actual output current measurement directly at the power supply unit (for devices at least 36 mm wide)
- cULus, cURus, NEC class 2, ABS, BV, DNV GL, LRS certifications
- LOGO!Power Ex 24 V/4.0 A, for use in Zone 2 hazardous environments (gases, vapors or mists)
Технические данные
Article number |
6EP3330-6SB00-0AY0 |
6EP3331-6SB00-0AY0 |
6EP3332-6SB00-0AY0 |
6EP3333-6SB00-0AY0 |
6EP3333-6SC00-0AY0 |
|
|---|---|---|---|---|---|---|
product brand name |
LOGO!Power |
LOGO!Power |
LOGO!Power |
LOGO!Power |
LOGO!Power |
|
type of current supply |
24 V/0.6 A |
24 V/1.3 A |
24 V/2.5 A |
24 V/4 A |
24 V/4 A |
|
General information |
||||||
Technical Product Detail Page |
||||||
input |
||||||
type of the power supply network |
1-phase AC or DC |
1-phase AC or DC |
1-phase AC or DC |
1-phase AC or DC |
1-phase AC or DC |
|
supply voltage at AC |
||||||
|
100 V |
100 V |
100 V |
100 V |
100 V |
|
|
240 V |
240 V |
240 V |
240 V |
240 V |
|
|
85 V |
85 V |
85 V |
85 V |
85 V |
|
|
264 V |
264 V |
264 V |
264 V |
264 V |
|
input voltage at DC |
110 ... 300 V |
110 ... 300 V |
110 ... 300 V |
110 ... 300 V |
110 ... 300 V |
|
wide range input |
Yes |
Yes |
Yes |
Yes |
Yes |
|
overvoltage overload capability |
300 V AC for 1 s |
300 V AC for 1 s |
300 V AC for 1 s |
300 V AC for 1 s |
300 V AC for 1 s |
|
buffering time for rated value of the output current in the event of power failure minimum |
40 ms |
40 ms |
40 ms |
40 ms |
40 ms |
|
operating condition of the mains buffering |
at Vin = 187 V |
at Vin = 187 V |
at Vin = 187 V |
at Vin = 187 V |
at Vin = 187 V |
|
line frequency |
50 Hz/60 Hz |
50 Hz/60 Hz |
50 Hz/60 Hz |
50 Hz/60 Hz |
50 Hz/60 Hz |
|
line frequency |
47 ... 63 Hz |
47 ... 63 Hz |
47 ... 63 Hz |
47 ... 63 Hz |
47 ... 63 Hz |
|
input current |
||||||
|
0.3 A |
0.7 A |
1.22 A |
1.95 A |
1.95 A |
|
|
0.2 A |
0.35 A |
0.66 A |
0.97 A |
0.97 A |
|
current limitation of inrush current at 25 °C maximum |
20 A |
25 A |
52 A |
31 A |
31 A |
|
I2t value maximum |
0.8 A²·s |
0.8 A²·s |
3 A²·s |
2.5 A²·s |
2.5 A²·s |
|
fuse protection type |
internal |
internal |
internal |
internal |
internal |
|
fuse protection type in the feeder |
Recommended miniature circuit breaker: from 6 A characteristic B or from 2 A characteristic C |
Recommended miniature circuit breaker: from 6 A characteristic B or from 2 A characteristic C |
Recommended miniature circuit breaker: from 10 A characteristic B or from 6 A characteristic C |
Recommended miniature circuit breaker: from 10 A characteristic B or from 6 A characteristic C |
Recommended miniature circuit breaker: from 10 A characteristic B or from 6 A characteristic C |
|
output |
||||||
voltage curve at output |
Controlled, isolated DC voltage |
Controlled, isolated DC voltage |
Controlled, isolated DC voltage |
Controlled, isolated DC voltage |
Controlled, isolated DC voltage |
|
output voltage at DC rated value |
24 V |
24 V |
24 V |
24 V |
24 V |
|
output voltage |
||||||
|
24 V |
24 V |
24 V |
24 V |
24 V |
|
24 V |
24 V |
24 V |
24 V |
24 V |
||
output voltage adjustable |
No |
Yes; via potentiometer |
Yes; via potentiometer |
Yes; via potentiometer |
Yes; via potentiometer |
|
adjustable output voltage |
22.2 ... 26.4 V |
22.2 ... 26.4 V |
22.2 ... 26.4 V |
22.2 ... 26.4 V |
||
relative overall tolerance of the voltage |
3 % |
3 % |
3 % |
3 % |
3 % |
|
relative control precision of the output voltage |
||||||
|
0.1 % |
0.1 % |
0.1 % |
0.1 % |
0.1 % |
|
|
0.1 % |
0.1 % |
0.1 % |
0.1 % |
0.1 % |
|
residual ripple |
||||||
|
200 mV |
200 mV |
200 mV |
200 mV |
200 mV |
|
|
30 mV |
30 mV |
30 mV |
30 mV |
30 mV |
|
voltage peak |
||||||
|
300 mV |
300 mV |
300 mV |
300 mV |
300 mV |
|
|
50 mV |
50 mV |
50 mV |
50 mV |
50 mV |
|
display version for normal operation |
Green LED for output voltage OK |
Green LED for output voltage OK |
Green LED for output voltage OK |
Green LED for output voltage OK |
Green LED for output voltage OK |
|
behavior of the output voltage when switching on |
No overshoot of Vout (soft start) |
No overshoot of Vout (soft start) |
No overshoot of Vout (soft start) |
No overshoot of Vout (soft start) |
No overshoot of Vout (soft start) |
|
response delay maximum |
0.5 s |
0.5 s |
0.5 s |
0.5 s |
0.5 s |
|
voltage increase time of the output voltage |
||||||
|
100 ms |
100 ms |
100 ms |
100 ms |
100 ms |
|
output current |
||||||
|
0.6 A |
1.3 A |
2.5 A |
4 A |
4 A |
|
|
0 ... 0.6 A; +55 ... +70 °C: Derating 2%/K |
0 ... 1.3 A; +55 ... +70 °C: Derating 2%/K |
0 ... 2.5 A; +55 ... +70 °C: Derating 2%/K |
0 ... 4 A; +55 ... +70 °C: Derating 2%/K |
0 ... 4 A; +55 ... +70 °C: Derating 2%/K |
|
0.0 ... 2.4 A |
0.0 ... 2.4 A |
2.5 A |
2.6 ... 4.9 A |
2.6 ... 4.9 A |
||
supplied active power typical |
14.4 W |
31.2 W |
60 W |
96 W |
96 W |
|
bridging of equipment |
No |
Yes |
Yes |
Yes |
||
number of parallel-switched equipment resources |
2 |
2 |
2 |
|||
efficiency |
||||||
efficiency in percent |
81 % |
86 % |
89.5 % |
89 % |
89 % |
|
power loss [W] |
||||||
|
3.4 W |
5.1 W |
7 W |
11.7 W |
11.7 W |
|
|
0.3 W |
0.3 W |
0.3 W |
0.3 W |
0.3 W |
|
closed-loop control |
||||||
relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical |
0.2 % |
0.2 % |
0.2 % |
0.2 % |
0.2 % |
|
relative control precision of the output voltage at load step of resistive load 10/90/10 % typical |
2 % |
1 % |
2 % |
2 % |
2 % |
|
setting time |
||||||
|
1 ms |
1 ms |
1 ms |
1 ms |
1 ms |
|
|
1 ms |
1 ms |
1 ms |
1 ms |
1 ms |
|
protection and monitoring |
||||||
design of the overvoltage protection |
< 60 V |
< 60 V |
< 60 V |
< 60 V |
< 60 V |
|
property of the output short-circuit proof |
Yes |
Yes |
Yes |
Yes |
Yes |
|
design of short-circuit protection |
Constant current characteristic |
Constant current characteristic |
Constant current characteristic |
Constant current characteristic |
Constant current characteristic |
|
|
0.8 A |
1.7 A |
3.2 A |
5 A |
5 A |
|
overcurrent overload capability |
||||||
|
150% Iout rated typ. 200 ms |
150% Iout rated typ. 200 ms |
150% Iout rated typ. 200 ms |
150% Iout rated typ. 200 ms |
150% Iout rated typ. 200 ms |
|
|
overload capability 150% Iout rated typ. 200 ms |
overload capability 150% Iout rated typ. 200 ms |
overload capability 150% Iout rated typ. 200 ms |
overload capability 150% Iout rated typ. 200 ms |
overload capability 150% Iout rated typ. 200 ms |
|
enduring short circuit current RMS value |
||||||
|
0.8 A |
1.7 A |
3.2 A |
5 A |
5 A |
|
measuring point for output current |
No |
Yes; 50 mV =^ 1.3 A |
Yes; 50 mV =^ 2.5 A |
Yes; 50 mV =^ 4 A |
Yes; 50 mV =^ 4 A |
|
safety |
||||||
galvanic isolation between input and output |
Yes |
Yes |
Yes |
Yes |
Yes |
|
galvanic isolation |
Output voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7) |
Output voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7) |
Output voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7) |
Output voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7) |
Output voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7) |
|
operating resource protection class |
Class II (without protective conductor) |
Class II (without protective conductor) |
Class II (without protective conductor) |
Class II (without protective conductor) |
Class II (without protective conductor) |
|
protection class IP |
IP20 |
IP20 |
IP20 |
IP20 |
IP20 |
|
EMC |
||||||
standard |
||||||
|
EN 55022 Class B |
EN 55022 Class B |
EN 55022 Class B |
EN 55022 Class B |
EN 55022 Class B |
|
|
not applicable |
not applicable |
not applicable |
EN 61000-3-2 |
EN 61000-3-2 |
|
|
EN 61000-6-2 |
EN 61000-6-2 |
EN 61000-6-2 |
EN 61000-6-2 |
EN 61000-6-2 |
|
standards, specifications, approvals |
||||||
certificate of suitability |
||||||
|
Yes |
Yes |
Yes |
Yes |
Yes |
|
|
Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273, NEC class 2 (acc. to UL 1310) |
Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273, NEC class 2 (acc. to UL 1310) |
Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273, NEC class 2 (acc. to UL 1310) |
Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273 |
Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950-1, CSA C22.2 No. 60950-1) File E151273 |
|
|
Yes |
|||||
|
Yes |
Yes |
Yes |
Yes |
||
|
Yes; according to UL1310, File E151273 |
Yes; according to UL1310, File E151273 |
Yes; according to UL1310, File E151273 |
No |
No |
|
|
Yes |
Yes |
Yes |
Yes |
||
type of certification |
||||||
|
Yes; R-41188271 |
Yes; R-41188271 |
Yes; R-41188271 |
|||
|
Yes |
Yes |
Yes |
Yes |
Yes |
|
MTBF at 40 °C |
4 415 040 h |
3 094 996 h |
2 864 520 h |
2 391 480 h |
2 391 480 h |
|
standards, specifications, approvals hazardous environments |
||||||
certificate of suitability |
||||||
|
No |
No |
No |
No |
Yes; IECEx Ex ec IIC T3 Gc |
|
|
No |
No |
No |
No |
Yes; ATEX (EX) II 3G Ex ec IIC T3 Gc |
|
|
No |
No |
No |
No |
Yes |
|
|
Yes |
|||||
|
Yes |
|||||
|
No |
No |
No |
No |
No |
|
standards, specifications, approvals marine classification |
||||||
shipbuilding approval |
Yes |
Yes |
Yes |
Yes |
No |
|
Marine classification association |
||||||
|
Yes |
Yes |
Yes |
Yes |
No |
|
|
Yes |
Yes |
Yes |
Yes |
Yes |
|
|
Yes |
Yes |
Yes |
Yes |
No; in preparation |
|
|
Yes |
Yes |
Yes |
Yes |
No |
|
standards, specifications, approvals Environmental Product Declaration |
||||||
Environmental Product Declaration |
Yes |
Yes |
Yes |
Yes |
Yes |
|
global warming potential [CO2 eq] |
||||||
|
94.5 kg |
141.9 kg |
195.3 kg |
326 kg |
326 kg |
|
|
1.3 kg |
2.3 kg |
3.8 kg |
5.5 kg |
5.5 kg |
|
|
93 kg |
139.5 kg |
191.4 kg |
320 kg |
320 kg |
|
|
0.05 kg |
0.08 kg |
0.14 kg |
0.2 kg |
0.2 kg |
|
Siemens Eco Profile (SEP) |
Siemens EcoTech |
Siemens EcoTech |
Siemens EcoTech |
Siemens EcoTech |
Siemens EcoTech |
|
ambient conditions |
||||||
ambient temperature |
||||||
|
-25 ... +70 °C; with natural convection |
-25 ... +70 °C; with natural convection |
-25 ... +70 °C; with natural convection |
-25 ... +70 °C; with natural convection |
-25 ... +70 °C; with natural convection |
|
|
-40 ... +85 °C |
-40 ... +85 °C |
-40 ... +85 °C |
-40 ... +85 °C |
-40 ... +85 °C |
|
|
-40 ... +85 °C |
-40 ... +85 °C |
-40 ... +85 °C |
-40 ... +85 °C |
-40 ... +85 °C |
|
environmental category according to IEC 60721 |
Climate class 3K3, 5 ... 95% no condensation |
Climate class 3K3, 5 ... 95% no condensation |
Climate class 3K3, 5 ... 95% no condensation |
Climate class 3K3, 5 ... 95% no condensation |
Climate class 3K3, 5 ... 95% no condensation |
|
connection method |
||||||
type of electrical connection |
screw terminal |
screw terminal |
screw terminal |
screw terminal |
screw terminal |
|
|
L, N: 1 screw terminal each for 0.5 ... 2.5 mm2 single-core/finely stranded |
L, N: 1 screw terminal each for 0.5 ... 2.5 mm2 single-core/finely stranded |
L, N: 1 screw terminal each for 0.5 ... 2.5 mm2 single-core/finely stranded |
L, N: 1 screw terminal each for 0.5 ... 2.5 mm2 single-core/finely stranded |
L, N: 1 screw terminal each for 0.5 ... 2.5 mm2 single-core/finely stranded |
|
|
+, -: 1 screw terminal each for 0.5 ... 2.5 mm² |
+, -: 1 screw terminal each for 0.5 ... 2.5 mm² |
+, -: 1 screw terminal each for 0.5 ... 2.5 mm² |
+, -: 1 screw terminal each for 0.5 ... 2.5 mm² |
+, -: 1 screw terminal each for 0.5 ... 2.5 mm² |
|
|
- |
- |
- |
- |
- |
|
mechanical data |
||||||
width × height × depth of the enclosure |
18 mm × 90 mm × 53 mm |
36 mm × 90 mm × 53 mm |
54 mm × 90 mm × 53 mm |
72 mm × 90 mm × 53 mm |
72 mm × 90 mm × 53 mm |
|
installation width × mounting height |
18 mm × 130 mm |
36 mm × 130 mm |
54 mm × 130 mm |
72 mm × 130 mm |
72 mm × 130 mm |
|
required spacing |
||||||
|
20 mm |
20 mm |
20 mm |
20 mm |
20 mm |
|
|
20 mm |
20 mm |
20 mm |
20 mm |
20 mm |
|
|
0 mm |
0 mm |
0 mm |
0 mm |
0 mm |
|
|
0 mm |
0 mm |
0 mm |
0 mm |
0 mm |
|
fastening method |
Snaps onto DIN rail EN 60715 35x7.5/15, direct mounting in different mounting positions |
Snaps onto DIN rail EN 60715 35x7.5/15, direct mounting in different mounting positions |
Snaps onto DIN rail EN 60715 35x7.5/15, direct mounting in different mounting positions |
Snaps onto DIN rail EN 60715 35x7.5/15, direct mounting in different mounting positions |
Snaps onto DIN rail EN 60715 35x7.5/15, direct mounting in different mounting positions |
|
|
Yes |
Yes |
Yes |
Yes |
Yes |
|
|
No |
No |
No |
No |
No |
|
|
Yes |
Yes |
Yes |
Yes |
Yes |
|
housing can be lined up |
Yes |
Yes |
Yes |
Yes |
Yes |
|
net weight |
0.07 kg |
0.12 kg |
0.2 kg |
0.29 kg |
0.29 kg |
|
further information internet links |
||||||
internet link |
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
additional information |
||||||
other information |
Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
|
security information |
||||||
security information |
Siemens provides products and solutions with industrial cybersecurity functions that support the secure operation of plants, systems, machines and networks. In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement - and continuously maintain - a holistic, state-of-the-art industrial cybersecurity concept. Siemens’ products and solutions constitute one element of such a concept. Customers are responsible for preventing unauthorized access to their plants, systems, machines and networks. Such systems, machines and components should only be connected to an enterprise network or the internet if and to the extent such a connection is necessary and only when appropriate security measures (e.g. firewalls and/or network segmentation) are in place. For additional information on industrial cybersecurity measures that may be implemented, please visit www.siemens.com/cybersecurity-industry. Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to cyber threats. To stay informed about product updates, subscribe to the Siemens Industrial Cybersecurity RSS Feed under . (V4.7) |
Siemens provides products and solutions with industrial cybersecurity functions that support the secure operation of plants, systems, machines and networks. In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement - and continuously maintain - a holistic, state-of-the-art industrial cybersecurity concept. Siemens’ products and solutions constitute one element of such a concept. Customers are responsible for preventing unauthorized access to their plants, systems, machines and networks. Such systems, machines and components should only be connected to an enterprise network or the internet if and to the extent such a connection is necessary and only when appropriate security measures (e.g. firewalls and/or network segmentation) are in place. For additional information on industrial cybersecurity measures that may be implemented, please visit www.siemens.com/cybersecurity-industry. Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to cyber threats. To stay informed about product updates, subscribe to the Siemens Industrial Cybersecurity RSS Feed under . (V4.7) |
Siemens provides products and solutions with industrial cybersecurity functions that support the secure operation of plants, systems, machines and networks. In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement - and continuously maintain - a holistic, state-of-the-art industrial cybersecurity concept. Siemens’ products and solutions constitute one element of such a concept. Customers are responsible for preventing unauthorized access to their plants, systems, machines and networks. Such systems, machines and components should only be connected to an enterprise network or the internet if and to the extent such a connection is necessary and only when appropriate security measures (e.g. firewalls and/or network segmentation) are in place. For additional information on industrial cybersecurity measures that may be implemented, please visit www.siemens.com/cybersecurity-industry. Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to cyber threats. To stay informed about product updates, subscribe to the Siemens Industrial Cybersecurity RSS Feed under . (V4.7) |
Siemens provides products and solutions with industrial cybersecurity functions that support the secure operation of plants, systems, machines and networks. In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement - and continuously maintain - a holistic, state-of-the-art industrial cybersecurity concept. Siemens’ products and solutions constitute one element of such a concept. Customers are responsible for preventing unauthorized access to their plants, systems, machines and networks. Such systems, machines and components should only be connected to an enterprise network or the internet if and to the extent such a connection is necessary and only when appropriate security measures (e.g. firewalls and/or network segmentation) are in place. For additional information on industrial cybersecurity measures that may be implemented, please visit www.siemens.com/cybersecurity-industry. Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to cyber threats. To stay informed about product updates, subscribe to the Siemens Industrial Cybersecurity RSS Feed under . (V4.7) |
Siemens provides products and solutions with industrial cybersecurity functions that support the secure operation of plants, systems, machines and networks. In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement - and continuously maintain - a holistic, state-of-the-art industrial cybersecurity concept. Siemens’ products and solutions constitute one element of such a concept. Customers are responsible for preventing unauthorized access to their plants, systems, machines and networks. Such systems, machines and components should only be connected to an enterprise network or the internet if and to the extent such a connection is necessary and only when appropriate security measures (e.g. firewalls and/or network segmentation) are in place. For additional information on industrial cybersecurity measures that may be implemented, please visit www.siemens.com/cybersecurity-industry. Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to cyber threats. To stay informed about product updates, subscribe to the Siemens Industrial Cybersecurity RSS Feed under . (V4.7) |
|
24 V |
24 V |
24 V |
24 V |
24 V |
||
24 V |
24 V |
24 V |
24 V |
24 V |
||
Дополнительно
SITOP redundancy modules |
For more information, visit: www.siemens.com/sitop-redundancy/mall |
SITOP selectivity modules |
For more information, visit: www.siemens.com/sitop-selectivity/mall |
SITOP BUF1200 buffer module |
For more information, visit: www.siemens.com/sitop-buffering/mall |
SITOP DC UPS |
For more information, visit: www.siemens.com/sitop-ups/mall |